Overview

The EGI VRF Adapter provides seamless integration between VRF HVAC systems and smart home or building management systems (BMS). Available in two versions—Tuya ZigBee or Modbus RTU (RS-485)—this adapter enables centralized control, automation, and monitoring of up to 32 indoor units (IDUs).

Versions

  • Tuya ZigBee Version:
    • Wireless ZigBee 3.0 communication
    • Compatible with Tuya Smart and Smart Life apps
    • Easily integrates with Home Assistant via Tuya integration
  • Modbus RTU Version:
    • RS-485 wired interface
    • Native Modbus RTU support
    • Integrates directly with BMS, KNX systems (via gateway), and Home Assistant Modbus integration

Applications

  • Residential smart homes
  • Commercial building management
  • Hospitality and healthcare facilities
  • Industrial environmental control

Integration & Compatibility

Home AssistantKNX IntegrationBSwitch (SwitcBee) Integration
Native integration via ModbusCompatible via standard Modbus RTU-to-KNX gateways.Direct RS-485 wired communication.

Can share the same power supply with CoolSwitch (12V DC).

Simple two-wire RS-485 connection (A to A, B to B).

Cloud integration via Tuya
Direct ZigBee integration (ZigBee2MQTT/ZHA) (under development)

Certifications & Compliance

RegionCertificateDirectives and compliances
European Union (EU)CE Mark

Radio Equipment Directive (RED, 2014/53/EU)

RF:

EN 300 328 (2.4 GHz)

EN 301 893 (5 GHz)

EMC:

EN 301 489-1

EN 301 489-17

Safety:

EN 62368-1

RF Exposure:

EN 62479 / EN 62311

RoHS ComplianceDirective 2011/65/EU
WEEE Directive

 

 

2012/19/EU
USA (Optional, upon request)FCC CertificationFCC Part 15C (2.4 GHz) and FCC Part 15E (5 GHz)
UL/ETL Safety CertificationUL 62368-1 (optional)
California Proposition 65Compliance (optional)
IsraelMinistry of Communications (MoC)Full certification and explicit report formats compliant with MoC standards
IISApproval compliant with Israeli standards

Technical Specifications

General
Operating Voltage 12-30 VDC (Typical 12VDC, 2W)
Communication InterfacesZigBee 3.0 (Tuya Version)

RS-485 Modbus RTU (Modbus Version)

InstallationDIN Rail mountable
Operating Temperature-10°C to 60°C
Storage Temperature-20°C to 70°C
Relative Humidity10%-90% (Non-condensing)
RS-485 Communication (Modbus Version Only)
Baud Rate9600 bps
Data Bits8
ParityEven
Stop Bits1
Slave ID1
ZigBee Communication (Tuya Version Only)
ProtocolZigBee 3.0
Frequency 2.4 GHz
Range Typically 30-50 meters (indoor)
Gateway CompatibilityAny standard Tuya ZigBee gateway
Inputs & Outputs
Modbus RTUA/B Terminals (RS-485)
VRF System ConnectionTerminals for VRF communication bus
Power SupplyDC Input terminal (12-30VDC)
Physical Dimensions
Dimensions (WxHxD)106mm x 90mm x 58mm
WeightApprox. 220 grams
MountingStandard DIN Rail (35mm)
IP RatingIP20 (For Indoor use only)

Supported VRF Brands


Brand
Adapter PortVRF PortPolarity RequiredConnection on ODUCentralized Control Address
Daikin (Multiple ODUs)F1, F2F1, F2 (external-external)NoYesYes
Daikin (Single ODU)F1, F2F1, F2 (internal-external)NoNoYes
Mitsubishi (Multiple ODUs)F1, F2M1, M2 (TB7)NoYesNo
Mitsubishi (Single ODU)F1, F2M1, M2 (TB3)NoNoNo
Mitsubishi (Rhombus)F1, F2M1, M2 (external/Split box)NoNoNo
HitachiF1, F21, 2NoNoNo
ToshibaF1, F2U1, U2NoNoYes
PanasonicF1, F2U1, U2NoNoNo
HisenseF1, F21, 2NoNoNo
HaierF1, F2P, QNoNoNo
York QingdaoF1, F21, 2NoNoNo
York GuangzhouX, YA2, B2YesYesNo
GREEH, LG1, G2YesYesNo
TCLH, LF1, F2YesNoNo
Mitsubishi Heavy IndustriesX, YA1, B1 or A2, B2NoNoNo
Midea, Bosch, CarrierX, YX, Y or P, QYesYesNo
AUXX, YA, BYesNoNo
SamsungX, YF1, F2NoNoNo
LGX, YA, B (CEN)YesNoNo
MacwellX, YApc, BpcYesYesNo
TICAX, YA3, B3YesNoNo
ChigoX, YP, QYesNoNo
TraneX, YA, BYesYesNo